				TURBINE PROTECTION SUMMARY
				This is What You Need to Know
				NFPA 850:
Recommends the water application rate for turbine protection at .30 gpm/ft2.
				FM Global Testing:
				Full scale testing proved .30 gpm/ft2 was inadequate to protect turbines and recommends .40 gpm/ft2 (Bulletin 2006-06)
				Dominion Testing:
				Testing showed educting 3% F-500 Encapsulator Agent into the water at .20 gpm/ft2 extinguished the fire three times faster than plain water at .40 gpm/ft2.
				UL Testing:
				Tests conducted at Underwriters Laboratories in 2014 showed .45 gpm/ft2 would be a better recommendation.
				UL Testing in 2014 showed supplementing an existing .30 gpm/ft2 suppression system with 3% F-500 EA is as effective as re-designing and installing a .45 gpm/ft2 water only system.
				FM GLOBAL RISK ASSESSMENT
				Fire Damage:
				Inadequately Protected Turbine with R480 million in damages and 24 weeks of shutdown
				Adequately Protected Turbine with only R1.8 million in damages and 2 weeks of shutdown
				Figures are from FM Global. Recent studies suggest the damage for one power plant is more likely closer to $100 million with loss of generating capacity exceeding 52 weeks.